Blauberg DC-F133B-EC-N07 133mm EC Dual Inlet Centrifugal Blower

Blauberg DC-F133B-EC-N07 133mm EC Dual Inlet Centrifugal Blower

The Blauberg DC-F133B-EC-N07 is a 133 mm, 115 VAC EC dual inlet centrifugal blower with up to 1100 m³/h airflow, IP44 protection and 0-10 V/PWM speed control.
Send Inquiry

MOQ:100 pcs· Standard lead time:15-25 days· Engineering sample.7-10 datys

Description
Technical Parameters

Suzhou Blauberg Motoren Technology Co., Ltd. is one of the leading manufacturers and suppliers of blauberg dc-f133b-ec-n07 133mm ec dual inlet centrifugal blower in China. Welcome to buy bulk high quality customized products made in China here and get quotation from our factory. For price consultation, contact us.

 

Basic Info

Model DC-F133B-EC-N07 Product Type EC Dual Inlet Centrifugal Blower
Phase 1~ Rated Voltage 115 VAC
Voltage Range 92–138 VAC Frequency 50/60 Hz
Nominal Speed 2300 ±150 RPM Max. Input Power 200 ±10 W
Max. Input Current 2 A Sound Level 75 dB(A)
Ambient Temperature -25 to +60 °C Certification CE, RoHS
Protection IP44 Insulation Class Class B

Technical Description

Dimensions 198 × 172 × 254 mm Motor Model EC092AC115V230W
Motor Size 92 mm Impeller Metal, 38 blades
Airflow Direction Side discharge Rotation Clockwise, viewed from rotor side
Housing / Rotor Stretched housing / blue powder-coated rotor Mounting Position Any position
Operating Mode S1 continuous duty Bearing Ball bearing
Cable Length 500 ±20 mm; extendable in 500 mm increments Humidity Operation 5%–90% RH; storage 5%–95% RH
Storage Temperature -40 to +80 °C Safety Class Class I; protective earth required
Motor Protection Locked rotor, thermal, over/undervoltage, overcurrent and soft start Control 0–10 VDC / PWM

Product Application

1 Charging Column 9 Equipment Cooling Project
2 Kitchen Smoke Exhaust System 10 Ventilation Unit Project
3 FFU Project 11 AHU Project
4 Computer Room Cooling 12 Air Purifier Project
5 Rail Transit Air-Conditioning 13 Heat Exchanger Project
6 Electrical Appliances 14 Telecom Container Project
7 FanGrid Project 15 Data Center Cooling Project
8 Ventilation Equipment Project 16 Industrial Cooling System

Air Performance

DC-F133B-EC-N07 Air Performance

Overall Dimensions

DC-F133B-EC-N07 Overall Dimensions

Electrical Connection

DC-F133B-EC-N07 Electrical Connection

Line Conn. Designation Colour Function / Assignment
Power Line   PE Green/Yellow Protective earth
Power Line U1 L Brown Mains power supply, live conductor
Power Line U2 N Blue Mains power supply, neutral conductor
Control Line U4 +10 V Red Fixed 10 VDC output, ±5%, max. 10 mA; external device supply; SELV
Control Line U5 Speed Control Yellow 0–10 V/PWM input; recommended PWM amplitude 10 V; SELV
Control Line U6 Signal Feedback White Tach output, 5 pulses/revolution; may be customised or changed to RD signal; SELV
Control Line U7 GND Blue Reference ground for control interface; SELV

Speed Control Settings

Control Method Operating Condition
Full speed Short the red (+10 V) and yellow (speed-control) conductors.
0–10 VDC Motor starts above 1.0 V and stops below 0.5 V.
PWM Frequency 1–10 kHz; recommended amplitude 10 V ±5%. Motor starts above 10% duty and stops below 5% duty.
Potentiometer A 10 kΩ potentiometer is recommended.

Note

1 Connect the power and control conductors strictly according to the wiring diagram.
2 Do not connect the white signal-feedback conductor directly to the red conductor or to an external DC power supply.
3 Shorting the red and yellow conductors applies the fixed 10 V reference and commands full speed.
4 If the blower does not start, check the speed-control input. Prevent injury from an unexpected start and never touch the rotor while energised.
5 Startup may take several seconds. Do not touch the impeller or rotor while energised or operating at low speed.
6 Before applying power, verify that the motor and blower assembly are installed securely.
7 Do not pull the cable. A damaged cable must be replaced by the manufacturer or authorised service personnel.
8 Do not drop, strike or wash the motor; moisture can reduce insulation performance and create a safety hazard.
9 Consult the manufacturer before using the product outside the agreed operating conditions.
10 The motor casing may remain hot for a short time after shutdown. Take measures to prevent burns.
11 Keep the housing clean and prevent debris from entering during installation.
12 Before initial operation, rotate the rotor by hand to confirm that there is no collision, interference or jamming.
13 The motor is part of the blower and must not be operated alone without an impeller or load.
14 For storage after unpacking, repack the product and keep it at -40 to +80 °C, RH ≤95%, in a clean ventilated area free of corrosive gases and at least 15 cm above the floor.
15 Install the blower out of children's reach and do not allow children to operate it.
16 The manufacturer reserves final interpretation of this specification.

Life and Maintenance, Warranty

1 The design life is 50,000 hours, limited by ball-bearing life at 40 °C. Actual service life depends on temperature, humidity, installation, load and the operating environment.
2 Clean and maintain the blower every 3–6 months, adjusted as appropriate for the operating environment.
3 The complete product is covered by a two-year warranty from the delivery date. Product-quality failures will be repaired or replaced. Damage caused by unauthorised disassembly, improper handling, human action, natural disaster or other force majeure is excluded.

Download

DC-F133B-EC-N07 Product Specification.pdf

 

Hot Tags: blauberg dc-f133b-ec-n07 133mm ec dual inlet centrifugal blower, China blauberg dc-f133b-ec-n07 133mm ec dual inlet centrifugal blower manufacturers, suppliers, factory, 146mm Double Inlet Forward Curved Blower, 146mm EC DC Double Inlet Centrifugal Fan, 146mm EC Double Inlet Blower Fan, Double Inlet Centrifugal Blowers, Industrial Double Inlet Forward Curved Fan, Inline Duct Centrifugal Fans