Model: GL-B310E-EC-05
Rated voltage: 230 VAC, 50/60 Hz
Rated speed: 2960 RPM
Maximum input power: 700 W; maximum input current: 3.1 A

MOQ:100 pcs· Standard lead time:15-25 days· Engineering sample.7-10 datys

Description
Technical Parameters

Suzhou Blauberg Motoren Technology Co., Ltd. is one of the leading manufacturers and suppliers of blauberg gl-b310e-ec-05 310mm ec plug fan in China. Welcome to buy bulk high quality customized products made in China here and get quotation from our factory. For price consultation, contact us.

 

The Blauberg GL-B310E-EC-05 is a 230 VAC EC backward-curved centrifugal plug fan with a support frame and eight-blade aluminum-alloy impeller. It operates at 2960 RPM and supports 0-10 VDC or PWM speed control, a status relay, RS485 Modbus communication and tachometer feedback.

Basic Info
Model GL-B310E-EC-05 Product Type EC Backward-Curved Centrifugal Plug Fan
Motor EC102AC230V750W-35 Phase 1~
Nominal Voltage 230 VAC Voltage Range 184-276 VAC
Frequency 50/60 Hz Data Method FA (Free Air)
Nominal Speed 2960 +/-5% RPM Maximum Input Power 700 W
Maximum Input Current 3.1 A Sound Level 85 dB(A)
Ambient Temperature -25 deg C to +60 deg C Conformity CCC, CE, RoHS
Technical Description
Dimensions 440 x 440 x 276.5 mm Motor Size 102
Impeller Aluminum alloy, 8 blades Air Flow Direction All around
Rotation Clockwise, viewed toward rotor Rotor Surface / Housing Blue plastic spraying / Stretch housing
Degree of Protection IP55 Insulation Class Class F
Duty / Bearing S1 / Ball bearing Installation Position Any
Speed Control 0-10 VDC / PWM, maximum PWM amplitude 10 VDC Voltage Output 10 VDC, maximum 10 mA
Protection PFC, status relay, locked-rotor, thermal, overvoltage, undervoltage, overcurrent and soft-start protection Cable Length 500 +/-20 mm
Dielectric Strength 1800 VAC / 50 Hz for 1 s; leakage current not over 10 mA; no breakdown or flashover Touch Current Not over 3.5 mA according to IEC 60990
Product Application
1 Charging Column 9 Equipment Cooling Project
2 Kitchen Smoke Exhaust System 10 Ventilation Unit Project
3 FFU Project 11 AHU Project
4 Computer Room Cooling 12 Air Purifier Project
5 Rail Transit Air-Conditioning 13 Heat Exchanger Project
6 Electrical Appliances 14 Telecom Container Project
7 FanGrid Project 15 Data Center Cooling Project
8 Ventilation Equipment Project 16 Industrial Cooling System
Air Performance

air-performance

Overall Dimensions

overall-dimensions

Electrical Connection

electrical-connection

Power and control wiring

Line Terminal Color Function
Power PE Green/Yellow Protective earth
Power U1 / L Brown Live conductor; supply voltage as specified
Power U2 / N Blue Neutral conductor; supply voltage as specified
Power U3 / NC White Status relay normally closed contact; opens on fault; 250 VAC / 2 A
Power U4 / COM Gray Status relay common contact; isolated; 250 VAC / 2 A
Control U5 / RSA Brown RS485 Modbus interface, RSA; SELV
Control U6 / RSB Gray RS485 Modbus interface, RSB; SELV
Control U7 / 0-10V/PWM Yellow 0-10 VDC or PWM input; maximum PWM amplitude 10 V; SELV
Feedback U8 / FG White Tachometer output, 5 pulses per revolution; SELV
Control U9 / +10V Red 10 VDC fixed output, +/-5%, maximum 10 mA; SELV
Control U10 / GND Blue Reference ground for control interface; SELV

Wiring diagram for signal feedbackSpeed setting

  • Full speed: short the red +10 VDC wire to the yellow VSP wire.
  • 0-10 VDC: the fan starts above 1.0 VDC and stops below 0.5 VDC.
  • PWM: 10 VDC +/-5% amplitude and 1-10 kHz. The fan starts above 10% duty and stops below 5%.
  • Potentiometer: use a recommended 10 kOhm potentiometer between red +10 VDC, yellow VSP and blue GND.

Tachometer feedback: 5 pulses per revolution. Fan speed n = 60f/a, where f is output frequency and a is pulses per revolution. The customer supplies Vfg and the pull-up resistor; Vfg = 3.3-30 VDC and R must be at least 1000 x Vfg ohms.

Notes
  1. Connect the power and control lines strictly according to the wiring diagram to prevent fan damage.
  2. Do not connect the white signal wire directly to the red signal wire or an external DC power supply.
  3. If the fan does not run after starting, check the speed-control input voltage and wiring. Do not touch the impeller or rotor after power is applied.
  4. The fan takes several seconds to start. Do not touch the impeller or rotor while energized or operating at low speed.
  5. Before switching on, confirm that the motor is installed securely.
  6. Do not pull the power cable. A damaged cable must be replaced by the manufacturer.
  7. Do not drop or strike the motor.
  8. Do not flush the motor; reduced insulation performance can cause electrical leakage.
  9. For applications outside the agreed operating conditions, consult Blauberg and obtain confirmation before use.
  10. The motor housing may remain hot shortly after the fan stops. Prevent direct contact and burns.
  11. During installation, keep the housing free of debris and clean the interior if necessary.
  12. Before installation and operation, rotate the rotor by hand and confirm there is no collision, interference or jamming.
  13. The motor is part of the fan and must not operate without an impeller or load.
  14. After unpacking, repackage the product for storage. Store it in a clean, ventilated warehouse at -40 deg C to +80 deg C, below 95% RH, without corrosive gases, and at least 15 cm above the floor.
  15. Install the fan out of reach of children and do not allow children to use it.
  16. The final interpretation of this specification belongs to Blauberg.

Life, maintenance and warranty

  1. Design life is 50,000 hours, limited by the ball-bearing life at 40 deg C. Actual service life depends on temperature, humidity, installation, fan load and other operating conditions.
  2. Clean and maintain the fan every 3-6 months according to the operating environment.
  3. The complete fan has a two-year warranty from the purchase date, subject to the delivery date. Product-quality failures are eligible for repair or replacement; damage caused by improper disassembly, handling, human action, natural disaster or force majeure is not covered.
Download

GL-B310E-EC-05 Product Specification.pdf

 

Hot Tags: blauberg gl-b310e-ec-05 310mm ec plug fan, China blauberg gl-b310e-ec-05 310mm ec plug fan manufacturers, suppliers, factory

Send Inquiry
Get in touch
Let's engineer your air solution.

Complete the form and our engineering team will contact you shortly.

bg